| Fire Alarm Control Panel FA-605/610 |
| Specification |
|
|
|
|
|
| Model |
|
FA-605 (5 Zone), FA-610 (10 Zone) |
| Power |
|
110/220VAC 50/60Hz |
|
| Voltage Scope |
|
Nominal voltage ± 20% |
|
| Standby Power |
|
24VDC 0.8Ah ~ 2.1Ah (battery backup) |
| Charging Voltage, Current |
|
26VDC 100mA ~ 400mA |
|
| Loop Voltage, Current |
|
24VDC short circuit under 5V 30mA |
| Exterior Resistance |
|
Round-trip under 50W |
|
| # of heat detector connected |
|
No limit |
|
|
|
| # of smoke detector connected |
|
30/loop |
|
|
|
| # of indicating lamp, bell connected |
|
# of loop x 1.2 |
|
|
| Digital Switch |
|
500000 Cycles Min. reliability |
|
| End of Line Resistor |
|
10 kW (one per loop) |
|
| Material |
|
1.2 mm steel plate |
|
|
| Color |
|
lvory white |
|
|
| Dimensions |
|
350 mm (H) x 285 mm (W) x 105 mm (D) |
| Accessory Functions |
|
Dual signal transfer contacts, aux.contacts |
| Fire Alarm Detector |
 |
|
Rate of Rise Heat Detector S-302 |
|
|
|
|
|
Effective Alert Area |
|
|
|
|
| |
construction/Height |
|
Under 4M |
|
4M ~ 8M |
| |
Fire-proof Building |
|
90 M2 |
|
45 M2 |
| |
Ordinary Building |
|
50 M2 |
|
30 M2 |
Specification |
| Type |
|
2-wire |
|
3-wire |
|
4-wire |
| Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
| |
|
|
|
|
|
0.4A @ 125VAC |
| Alarm Temperature |
|
Comply to EN54, CNS |
|
|
|
|
| Voltage Range |
|
12 ~ 30VDC |
|
|
|
|
|
|
| Alarm Current |
|
25 mA |
|
|
|
|
|
|
| Ambient Temperature |
|
0°C ~ +55°C |
|
|
|
|
| Material |
|
Fire-proof plastic |
|
|
|
|
| Dimensions |
|
102 mm (Dia) x 45 mm (H) |
|
|
| Weight |
|
About 130g |
|
|
|
|
|
|
| Color |
|
White |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Fixed Temperature Detector S-318 |
 |
Effective Alert Area |
|
|
|
|
| construction/Height |
|
Under 4M |
|
4M ~ 8M |
| Fire-proof Building |
|
60 M2 |
|
55 M2 |
| Ordinary Building |
|
30 M2 |
|
15 m2 |
Specification |
| Type |
|
2-wire |
|
3-wire |
|
4-wire |
| Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
| |
|
|
|
|
|
0.4A @ 125VAC |
| Thermal Setting |
|
70°C or other selections |
|
|
|
|
| Alarm Temperature |
|
Comply to EN54, CNS |
|
|
|
|
| Voltage Range |
|
12 ~ 30VDC |
|
|
|
|
|
|
| Alarm Current |
|
25 mA |
|
|
|
|
|
|
| Ambient Temperature |
|
-10°C ~ +55°C |
|
|
|
|
| Material |
|
Comply to EN54, CNS |
|
|
|
|
| Dimensions |
|
102 mm (Dia) x 47 mm (H) |
|
|
| Weight |
|
About 100g |
|
|
|
|
|
|
| Color |
|
White |
|
|
|
|
|
|
|
|
|
|
|
|
|
| Photoelectric Smoke Detector S-314 |
 |
Effective Alert Area |
|
|
|
|
| construction/Height |
|
Under 4M |
|
4M ~ 8M |
| Area Covered |
|
150 M2 |
|
75 M2 |
| Specification |
| Type |
|
2-wire |
|
3-wire |
|
4-wire |
| Alarm Contact |
|
N/A |
|
N/A |
|
0.8A @ 30VDC |
| |
|
|
|
|
|
0.4A @ 125VAC |
| Operating Sensitivity |
|
Comply to UL268, EN54, CNS |
|
|
| Operating Current |
|
DC 24V under 30 m |
|
|
|
|
| Monitoring Current |
|
Under 75 mA |
|
|
|
|
| Ambient Temperature |
|
-10°C ~ +55°C |
|
|
|
|
| Material |
|
Fire-proof plastic |
|
|
|
|
| Dimensions |
|
102 mm (Dia) x 50 mm (H) |
|
|
| Weight |
|
About 170g |
|
|
|
|
|
|
| Color |
|
White |
|
|
|
|
|
|
| Manual Call Point |
| Application |
|
S-334/S-335(with Base) |
|
| Adopted Voltage |
|
18 ~ 28VDC(24VDC) |
|
| Adopted Current |
|
100mA |
|
|
|
| Function |
|
Push Button Emergency, |
|
| |
|
Phone Jack, Reset Switch, |
|
| |
|
confirmation LED lamp |
|
| Coloe |
|
Red |
|
|
|
| Size |
|
138mm x 48mm/138mm x 70mm |
| Weight |
|
150g/270g |
|
|
| Joint Volume |
|
30VDC 1A |
|
|
 |
| Fire Alarm Bell 6" |
|
|
|
|
|
| Voltage |
|
24VDC |
|
|
|
| Current |
|
25mA |
|
|
|
| Sound Output |
|
93dBA@1M |
|
|
| Movement |
|
Motor, Pinion and Striker |
|
| Movement |
|
DC motor, acetral gear wheel |
|
| Feature |
|
steel striker |
|
|
| Gong |
|
Steel, secured with screw |
|
| Base Plate |
|
Molded black polycarbonate |
|
| Dimensions |
|
6" (152mm) |
|
|
| Weight |
|
850g |
|
|
|
Spray Test Smoke
[ Back ]
|
|
|
|
 |
|